IEEE Transactions on Power Delivery · 2006 · 134 citations · 8 references
EngineeringElectrical EngineeringCircuit TheoryElectromagneticsPower ElectronicsElectrical MeasurementElectrical System DiagnosticsFrequency ResponseInsulation MaterialsInsulation SystemsPower QualityFrequency-domain Response AnalysisInsulation DiagnosticsInsulation MonitoringInsulation Systems For WindingsThree-phase Circuit ModelingTransformer Insulation
This paper explores the possibility for using frequency response analysis (FRA) technique to characterize the quality of transformer insulation. For this purpose, a single-phase and a three-phase lumped parameter circuit models were developed. The single-phase model represents a transformer without a laminated core, whereas the three-phase model represents a real transformer with core. Calculations of frequency dependent circuit parameters are presented and the effects imparted on the frequency response by different loss mechanisms (in insulation, in windings and in core) are discussed. The simulations are compared with results of measurements on real objects. It is shown that FRA could be used for insulation diagnostics if the measurements were of high enough quality.
8