IEEE Transactions on Power Systems · 2006 · 219 citations · 14 references
EngineeringElectrical EngineeringEnergy SystemsRenewable Energy SystemsSchedulingConstraint-based SchedulingPower Grid AnalysisPower SystemsBenders DecompositionConstraintsDispatch ModelingLoad SheddingOptimal Power DispatchPower Generation SchedulingPower RegulationUnit Commitment
In this paper, an effective ac corrective/preventive contingency dispatch over a 24-h period is proposed based on security-constrained unit commitment (SCUC) model. The SCUC model includes unit commitment, ac security-constrained optimal power flow (SCOPF), and load shedding (LS) for steady state and contingencies. The objective of this SCUC model is to obtain the minimum bid-based system operating cost while maintaining the system security. The prevailing generation constraints, such as hourly power demand, system reserves, fuel and emission limits, ramp up/down limits, and minimum up/down time limits, are included in this model. In addition, system constraints such as time-limited emergency controls for a given contingency and ac network security limits are taken into account. The proposed ac solution for the hourly scheduling of generating units is based on Benders decomposition. Case studies with the six-bus system, the IEEE 118-bus test system, and 1168-bus system are presented in detail in this paper.
14
S.J. Wang, Mohammad Shahidehpour, Daniel S. Kirschen et al. · IEEE Transactions on Power Systems · 1995 · 538 citations
Natural Sciences, Industrial Engineering, Energy Systems +16
Further developments in LP-based optimal power flow
O. Alsaç, Joseph M. Bright, M. Prais et al. · IEEE Transactions on Power Systems · 1990 · 524 citations