Journal of Fire Sciences · 2004 · 18 citations · 6 references
EngineeringEarth SciencesCombustionFire ManagementFire Protection EngineeringFire DynamicsFire HazardsFire ModelingFire WeatherFlame PropagationFuel DynamicsBuoyant PlumesEmpirical Prediction EquationsExperimental StudiesFire Plume ModelingFire PlumesPlume Front DynamicsPlume RisePool Fires
Experimental studies were conducted in the PolyU/USTC Atrium to investigate the rise-time of buoyant plume front induced by pool fires. Through a series of full-scale burning tests, three semi-empirical equations were derived to predict the rise-time of buoyant plume front induced by a fire at three positions. These three positions are at the centre, near a wall and in the corner of the atrium floor respectively. The rise-time in dimensionless form and the plume radius equation are analyzed based on the measured data.
6
Natural smoke filling in atrium with liquid pool fires up to 1.6 MW
W. K. Chow, Ying Zhen Li, E. Cui et al. · Building and Environment · 2001 · 87 citations
Experimental Studies on Natural Smoke Filling in Atria
W. K. Chow, E. Cui, Y.Z. Li et al. · Journal of Fire Sciences · 2000 · 30 citations
Rise of plume front from starting fires
Gunnar Heskestad · Fire Safety Journal · 2001 · 13 citations