Analyzing Dynamic Interaction of Control Loops in the Time Domain

F. Michiel Meeuse, Adrie E. M. Huesman

Industrial & Engineering Chemistry Research · 2002 · 10 citations · 4 references

Concepts

Abstract

Process control structures are still mainly based on multiple interacting single-input single-output loops. The well-known relative gain array (RGA) is often used as an indication of the amount of interaction in the system. The RGA is limited in the sense that it is based only on static responses. We extend the RGA to compare the entire time domain open- and closed-loop step responses as interaction measurements. The closed-loop response is based on the best achievable control performance using internal model control. The results are shown graphically by regarding the open- and closed-loop responses of each pairing as a parametric representation. For each possible pairing, a graph is produced and placed in an array. This dynamic array is completely consistent with the static RGA and a useful extension in the case that the static RGA might prefer the wrong pairing (because the dynamics have been excluded) or does not prefer any pairing (when all RGA elements have more or less the same value).