IEEE Transactions on Power Delivery · 1999 · 23 citations · 14 references
Natural SciencesElectrical EngineeringPhysicsAtmospheric ElectricityFire Protection EngineeringPlasma PhysicsInsulation SystemsLightning CurrentLightning PhysicsThunderstorm ElectricityThunderstorm ElectrificationTransmission LinesElectric Field LinesFlashoverImpulse PropagationLightning Current In Power SystemsLightning Flashover AnalysisLightning Wave PropagationTractionVoltage
Insulation failure in medium voltage (10-20 kV) and electric traction lines (3 kV DC) is mainly due to indirect and direct lightning strokes to the lines. The overvoltages stressing the insulation have an impulse shape with a very short tail, much shorter than the standard 1.2/50 /spl mu/s wave. The paper presents the results of experimental tests performed with a 1.2/4 /spl mu/s wave, on air gaps and insulators in use in the lines under consideration. The flashover probability distributions and the voltage-time to breakdown characteristics under 1.2/4 /spl mu/s waves determined are presented and compared with the 1.2/50 /spl mu/s.
14