IEEE Transactions on Power Delivery · 1993 · 13 citations · 3 references
EngineeringElectrical EngineeringPhysicsCircuit TheoryPower ElectronicsReactor PhysicsElectrical System DiagnosticsElectrical System TestingPower QualityReactor Protection SystemsVoltage RegulationCircuit Breaker ProtectionCircuit Breaker TestingPhase AngleReignitionShort-circuit AnalysisShort-circuit ProtectionTest FacilitiesVoltage Interruption
Field measurement and computer analysis concerning 150 MVA shunt reactor current interruptions at a 275 kV gas insulated substation (GIS) were carried out to verify that high-frequency current interruptions can be caused by certain system structures on the circuit breaker power supply side. A shunt reactor current-interrupting test was conducted with phase angle control, which is considered to be the best method for preventing multiple reignitions, using short-circuit test facilities. The possibility of stable reignition-free interruption was confirmed, even when the longest arcing time is preset.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>