Investigations of multiple reignition phenomena and protection scheme of shunt reactor current interruption in GIS substations

Shigemitsu Okabe, M. Kosakada, H. Toda, Koji Suzuki, Masayuki Ishikawa

IEEE Transactions on Power Delivery · 1993 · 13 citations · 3 references

Concepts

Abstract

Field measurement and computer analysis concerning 150 MVA shunt reactor current interruptions at a 275 kV gas insulated substation (GIS) were carried out to verify that high-frequency current interruptions can be caused by certain system structures on the circuit breaker power supply side. A shunt reactor current-interrupting test was conducted with phase angle control, which is considered to be the best method for preventing multiple reignitions, using short-circuit test facilities. The possibility of stable reignition-free interruption was confirmed, even when the longest arcing time is preset.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>