IEEE Transactions on Power Apparatus and Systems · 1983 · 23 citations · 6 references
ArchitectureElectrical EngineeringBuilding MaterialsHeat TransferLifespan DevelopmentDurabilityInsulation MaterialsInsulation SystemsMaterial Degradation AssessmentService LifeEntrapmentInsulation AgingInsulation Degradation AssessmentInsulation DurabilityInsulation Systems For WindingsInsulation Thermal AgingSupersaturationTransformer Insulation
A power transformer life model and its related, test procedure have been evaluated and found to provide more meaningful information on retained operational capability of the winding insulation than can be derived from simple material tests. Both paper and enamel conductor insulation demonstrated retained functional ity after aging for time periods in excess of 5 times the life defined in industry loading guides. In addition, valuable knowledge was revealed about the behavior of conductor turn insulation with free gas entrapment, where the gas source was either oil supersaturation with dissolved gas or thermal evolution from overheated cellulose.
6
The Effect of Transformer-Oil-Preservation Methods on the Dielectric Strength of Oil
R. B. Kaufman, J. L. Pierce, E. Uhlig · Transactions of the American Institute of Electrical Engineers Part III Power Apparatus and Systems · 1957 · 12 citations
Natural Sciences, Materials Engineering, Preservation Technology +10