IEEE Transactions on Power Electronics · 2013 · 248 citations · 33 references
EngineeringElectrical EngineeringEnergy SystemsPower ElectronicsRenewable Energy SystemsDistributed Energy ResourcesMicrogridsPower Electronics For Renewable EnergyPower Grid AnalysisPower QualityRenewable Energy Power ConversionActive Harmonic FilteringCurrent ControlDecoupled ControlDistributed GenerationHarmonic MitigationHarmonic ReductionPhase-locked LoopsPower Quality Improvement
The increasing application of nonlinear loads may cause distribution system power quality issues. This paper proposes an enhanced current‑control approach that enables DG unit interfacing converters to actively compensate harmonics while maintaining primary power generation, and examines its performance when connected to a grid with frequency deviation. The controller features two decoupled branches for fundamental and harmonic currents, obviating the need for local harmonic current or voltage detection, and employs a closed‑loop power control scheme that derives the fundamental current reference without a PLL, thereby eliminating steady‑state tracking errors. Accurate power control is achieved even with harmonic compensation active, and simulated and experimental results from a single‑phase DG unit validate the proposed method.
The increasing application of nonlinear loads may cause distribution system power quality issues. In order to utilize distributed generation (DG) unit interfacing converters to actively compensate harmonics, this paper proposes an enhanced current control approach, which seamlessly integrates system harmonic mitigation capabilities with the primary DG power generation function. As the proposed current controller has two well-decoupled control branches to independently control fundamental and harmonic DG currents, local nonlinear load harmonic current detection and distribution system harmonic voltage detection are not necessary for the proposed harmonic compensation method. Moreover, a closed-loop power control scheme is employed to directly derive the fundamental current reference without using any phase-locked loops (PLL). The proposed power control scheme effectively eliminates the impacts of steady-state fundamental current tracking errors in the DG units. Thus, an accurate power control is realized even when the harmonic compensation functions are activated. In addition, this paper also briefly discusses the performance of the proposed method when DG unit is connected to a grid with frequency deviation. Simulated and experimental results from a single-phase DG unit validate the correctness of the proposed methods.
33
Pedro Rodríguez, Álvaro Luna, Jose Ignacio Candela et al. · IEEE Transactions on Industrial Electronics · 2010 · 1.1K citations · Full text