Electrical aging lifetime model of oil-impregnated paper under pulsating DC voltage influenced by temperature

Jian Li, Zhiman He, S. Grzybowski

IEEE Transactions on Dielectrics and Electrical Insulation · 2013 · 33 citations · 18 references

Concepts

Abstract

Main insulation of windings connected with valves in high voltage direct current (HVDC) convert transformers withstands pulsating DC voltages. This paper presents breakdown properties of oil-impregnated paper under pulsating DC voltages at different temperatures. Progressive stress tests were carried out to obtain breakdown voltages of oil-impregnated paper with thickness of 0.2 mm under pulsating DC voltages at different temperatures. Constant stress tests were executed to measure time to breakdown of the oil-paper specimens. Both types of the experiments were also undertaken under either AC or DC voltages. An electrical aging lifetime model was proposed for the oil-impregnated paper, and parameters of the electrical aging lifetime model were presented. Experiments and analysis results show that the breakdown voltages and time to breakdown of oil-paper insulation are influenced by temperature significantly.

References