Applied Physics Letters · 2013 · 19 citations · 4 references
EngineeringElectrical EngineeringPhysicsElectromagneticsElectromagnetismPower ElectronicsDielectricsElectric FieldsElectrical MeasurementElectro-optic EffectsCharge-coupled Device SensitivityElectric Field DistributionElectric Field IntensityElectric Field UniformityHigh-voltage InsulationKerr EffectSpace Charge DistributionTransformer Insulation
Transformer oil is the most widely used dielectric liquid for high voltage insulation. Measurements of the electric field distribution in high voltage pulsed transformer oil are of both practical and theoretical interests. Due to its low Kerr constant, previous electro-optic measurements with transformer oil rely on a technique called ac modulation, which works only for dc steady-state electric field mapping. With the help of a high-sensitivity charge-coupled device, we directly measure the Kerr electro-optic effect between parallel electrodes in transformer oil stressed by high voltage pulses. This work aims at demonstrating the reliability and evaluating the sensitivity of the measurements for three cases with identical electrodes: space-charge free, uniform electric field in the mid-region of the gap; space-charge free, non-uniform fringing electric field; and space charge distorted electric field in the mid-region of the gap. Future directions to improve accuracy by identifying and handling various sources of error and noise are suggested.
4
Electrical field distribution in transformer oil
U. Gäfvert, A. Jaksts, C. Törnkvist et al. · IEEE Transactions on Electrical Insulation · 1992 · 155 citations
Electric and Magnetic Double Refraction
J. W. Beams · Reviews of Modern Physics · 1932 · 78 citations