Concepedia

Publication | Closed Access

JCPDS—International Centre for Diffraction Data round robin study of silver behenate. A possible low-angle X-ray diffraction calibration standard

206

Citations

8

References

1995

Year

Abstract

A task group of the JCPDS—International Center for Diffraction Data (ICDD) was established with the charge of investigating the use of silver behenate, CH 3 (CH 2 ) 20 COO·Ag, as a possible low-angle calibration standard for powder diffraction applications. Utilizing several data collection and analysis techniques, long-period spacing ( d 001 ) values with a range of 58.219–58.480 Å were obtained. Using the same collected data and one data analysis refinement calculation method resulted in dm values with a range of 58.303–58.425 Å. Data collected using a silicon internal standard and the same singular data analysis calculation method provided d 001 values with a range of 58.363–58.381 Å.

References

YearCitations

Page 1