Heat Transfer Engineering · 2012 · 56 citations · 20 references
EngineeringElectrical EngineeringMechanical EngineeringEnergy SystemsHeat TransferThermal AnalysisCooling SystemsHeat PumpsHeat Recovery SystemsRefrigerationRefrigeration SystemsThermal ManagementCoolingData Center CoolingEnergy RecoveryMicrochannel CoolingSecond-law AnalysisThermal CyclesVapor Compression CoolingVapor Compression Cycle
This article highlights the advantages of on-chip microchannel cooling technology, based on first- and second-law analysis and experimental tests on two types of cooling cycles, the first driven by an oil-free liquid pump and the second by an oil-free vapor compressor. The analysis showed that the drivers of the fluid were the main culprits for major losses. It was further found that when energy recovery is of importance, making use of a vapor compression cycle increases the quality of the recovered energy, hence increasing its value. This was demonstrated by analyzing the synergy that can exist between the waste heat of a data center and heat reuse by a coal-fired power plant. It was found that power-plant efficiencies can be increased by up to 6.5% by making use of a vapor compression cycle, which results not only in significant monetary savings, but also in the reduced overall carbon footprints of both the data center and the power plant.
20
State of the Art of High Heat Flux Cooling Technologies
Bruno Agostini, M. Fabbri, Jung Eung Park et al. · Heat Transfer Engineering · 2007 · 633 citations · Full text
Engineering, Computer Engineering, Mechanical Engineering +17
Rémi Revellin, Vincent Dupont, Thierry Ursenbacher et al. · International Journal of Multiphase Flow · 2006 · 258 citations · Full text