IEEE Transactions on Power Apparatus and Systems · 1982 · 27 citations · 8 references
NursingElectrical EngineeringEmergencyEmergency ManagementEmergency Preparedness In The WorkplaceElectrical Hazard AssessmentElectrical Hazard IdentificationElectrical SafetyShock WavesElectric Shock Hazard AnalysisElectrical Shock ProtectionGround Shock AssessmentGrounding SystemsLow-voltage SafetyShock Hazard AssessmentShock Hazard Prevention
Breakdowns and disconnect switch operations in gas insulated switchgear (GIS) generate short duration high potentials on the grounded GIS enclosures. These high potentials cause breakdowns between the GIS enclosures and other nearby grounded components, and have resulted in low voltage protection and control wiring failures and personnel shocks. The mechanism of the transient ground rise phenomenon and the equipment related problems are discussed in two companion papers. The question of the degree of personnel shock hazard imposed by transient ground rise is discussed in this paper. The physiological effects of short duration impulses are reviewed and it is concluded that further biomedical research is required.
8
Safe Substation Grounding-Part I
J. Sverak, Warren A. Dick, Thomas Dodds et al. · IEEE Transactions on Power Apparatus and Systems · 1981 · 62 citations
Response to passage of electric current through the body.
A new electrical hazard associated with the electrocautery.
Geddes La, Tacker Wa, P. Cabler · PubMed · 1975 · 21 citations