Distribution transformer overloading capability under cold-load pickup conditions

J. Aubin, R. Bergeron, R. Morin

IEEE Transactions on Power Delivery · 1990 · 58 citations · 1 references

Concepts

Abstract

Greater use of electric heating in residential areas in North America has led to the appearance of a new type of thermal stress resulting from service restoration following a power outage. This loading condition, known as cold-load pickup, is simulated on a sample of 18 distribution transformers by applying overloads up to three times the rated current at ambient temperatures as low as -40 degrees C. The data gathered is used to develop a thermal model representing the transient behavior of distribution transformers. The results are then generalized to produce a loading guide for evaluation of maximum hot-spot temperatures and loss of life under given cold-load pickup conditions.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>