Effect of oil viscosity on transformer loading capability at low ambient temperatures

J. Aubin, Y. Langhame

IEEE Transactions on Power Delivery · 1992 · 53 citations · 3 references

Concepts

Abstract

The applicability of the ANSI loading guide for power transformers is limited to ambient temperatures above 0 degrees C because the thermal model does not account for variations in the oil viscosity and winding resistance. A practical calculation method based on the bottom-oil temperature and the surface temperature at the top of the cooling duct has been developed. Results indicate that the proposed thermal model could provide a sound basis for calculating the overload capacity for ambient temperatures below 0 degrees C or for severe overloads of short duration.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>