IEEE Transactions on Power Delivery · 1990 · 15 citations · 1 references
EngineeringElectrical EngineeringPhysicsCircuit TheoryPower ElectronicsTest ConstructionCurrent DistributionCurrent-voltage CharacteristicsElectrical System DiagnosticsElectrical System TestingPower QualityPower System ReliabilityCircuit Breaker ReliabilityCircuit Breaker TestingPower System TestingVoltage
A single-phase synthetic test method for evaluating the shunt capacitor switching performance of circuit breakers is proposed. The most important factor for evaluating the performance of a shunt capacitor switch is restriking, which is mainly influenced by the inrush current and the recovery voltage. A synthetic test circuit comprised of a current source, a voltage source, and the high-frequency current source is designed to evaluate vacuum circuit breakers. Results show that this method is especially suitable for obtaining a restriking probability distribution.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>
1