Acta Anaesthesiologica Scandinavica · 2006 · 24 citations · 11 references
MedicineAnesthesiologySurgeryAnesthesiaFire Protection EngineeringPerioperative SafetyFire PreventionFire SafetyFire TestingInhalation InjuryThermal Injury PreventionFire-related Injury PreventionFiresIgnition CharacteristicsLight Source EffectsMann - Whitney U TestOperating Room Fire PreventionOperating Room Fire SafetySmoke Spread
BACKGROUND: Fiberoptic light sources have been identified as a fire ignition mechanism in the operating room. This study attempted to determine whether a forced-air warming blanket (FAWB) could affect the ignition or spread of fire caused by a fiberoptic light source. METHODS: We exposed surgical drapes to a fiberoptic light source at close range. The results were categorized according to time to first smoke and damage resulting at 1 min. Data were analyzed using the Mann-Whitney rank-sum test. RESULTS: The sums of the rank values for the components of the drape indicated that there was a greater than 96.8-99.2% chance that the FAWB accelerated the time to first smoke. The FAWB appeared to protect the patient gown from damage during all trials. The presence of an FAWB under a surgical drape accelerated the time to first smoke when exposed to unprotected fiberoptic light sources, yet prevented damage to the underlying patient gown. In an actual surgical setting, it is likely that the FAWB would offer some protection to the patient's skin directly below the surgical drape. CONCLUSION: It is likely that the FAWB can offer some protection to the patient should an unprotected fiberoptic light source cause a fire.
11
Fire in the Operating Room During Tracheostomy
Jerome W. Thompson, Wayne Colin, Todd Snowden et al. · Southern Medical Journal · 1998 · 41 citations
Medicine, Anesthesiology, Surgery +13
Flammable Surgical Drapes???A Patient and Personnel Hazard
Ralph A. Milliken, D Bizzarri · Anesthesia & Analgesia · 1985 · 35 citations
Medicine, Anesthesiology, Surgery +17
D. J. Stouffer · Journal of Burn Care & Rehabilitation · 1992 · 33 citations
Engineering, Surgery, Anesthesia +16