Laboratory tests to evaluate HVDC wall bushing performance in wet weather

P.J. Lambeth

IEEE Transactions on Power Delivery · 1990 · 25 citations · 6 references

Concepts

Abstract

Two test methods are developed to simulate the conditions causing flashover of DC wall bushings at working voltage. One is based on the clean-fog pollution test. The other is a rain test, with part of the bushing unwetted. The effect of varying test parameters is measured and five variants of rain test are adopted for measuring the performance of a wall bushing. Its performance compared unfavorably with that of an empty porcelain shell. Various numbers of booster sheds (removable silicone-rubber cones fitted round the bushing) are found to improve its performance substantially.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>