Experimental and Numerical Studies on Adiabatic Flow of HFC Mixtures in Capillary Tubes

S. D. Chang, S. T. Ro

Purdue e-Pubs (Purdue University System) · 1996 · 11 citations · 5 references

Full text

Open access

Concepts

Abstract

This work presents the experimental and numerical studies on the adiabatic flow of HFC mixtures in capillary tubes.Two capillary tubes of inner diameter of 1.2 and 1.6mm with length of I .5mwere tested.The condensation temperatures of 40, 45, and 50C, and the subcooling temperatures ranging from 3 to l2C were chosen as operating conditions.The numerical model developed in this study has considered the effects of the underpressure for vaporization.kinetic energy of the refrigerant during expansion, and roughness of capillary tube.This work presents characteristic charts and correction factors for HFC-32/125/I34a. NOMENCLATURE c'-C4Coefficient in equation ( 2) Re Reynolds number ('=Gdll,l) Subscripts D Inner diameter of condenser, m T Temperature, oc bubble Bubble point d Inner diameter of capillary tube, m tlT,ub Degree of subcooling, "C cond Condensation f Friction factor v Specific volume, m 3 /kg dew Dew point G Mass flux, kg/m 2 s -Axial coordinate, m fg Saturated liquid, vapor h Specific enthalpy.kJ/kg E Roughness, m in Inlet LJ.

References

5