International Telecommunications Energy Conference · 2003 · 18 citations · 2 references
EngineeringElectrical EngineeringSystems EngineeringAutomationPower ElectronicsProcess ControlControl SystemsPower SystemsAutomation ElectronicsBattery Energy StorageControl System ReliabilityLine-interactive UpsOutput CharacteristicsSpace-saving StorageSurgeSurge Phenomena
A line interactive type UPS using a novel control system is described. The dynamic output characteristics have responded to tolerance band of the ITI (CBEMA) curve by using the proposed control system. Moreover, whereas voltage dip (<about 1 cycle), sag or surge occurs, a storage battery does not discharge due to charge from an inner capacitor and output characteristics are kept within the tolerance band. Therefore, the developed line interactive type UPS is satisfied with the recent needs from the global and environmental perspective, such as high reliability, high efficiency, space saving and low cost. In order to satisfy with the tolerance band of the ITI curve, the developed line interactive type UPS is suitable for information equipments.
2
Parallel processing inverter system
T. Kawabata, N. Sashida, Y. Yamamoto et al. · IEEE Transactions on Power Electronics · 1991 · 66 citations
A new international UPS classification by IEC 62040-3
Wilhelm Solter · 2003 · 53 citations