Nuclear Technology · 2014 · 11 citations · 9 references
EngineeringSystems EngineeringProcess ControlProcess SafetyProcess Systems EngineeringFailure AnalysisFailure Mode AnalysisFailure TheoriesFault DetectionFault DiagnosisHuman ReliabilityControl System ModelingDigital ControlDigital Control SystemsFailure ModesFault AnalysisOperator ReliabilityPressurization Failure ModesPressurized Water Reactors
A methodology comprising Dynamic Flowgraph Methodology (DFM) and A Technique for Human Error Analysis (ATHEANA) is applied to a digital control system proposed for the pressurizer of current pressurized water reactor plants. The methodology consists of modeling this control system and its interactions with the controlled process and operator through an integrated DFM/ATHEANA approach. The results were complemented by the opinions of experts in conjunction with fuzzy theory. In terms of human reliability, DFM, along with ATHEANA, can model equipment failure modes, operator errors (omission/commission), and human factors that, combined with plant conditions, influence human performance. The results show that the methodology provides an efficient fault analysis of digital systems identifying all possible interactions among components. Through prime implicants, the methodology shows the event combinations that lead to system failure. Quantitative results obtained are in agreement with literature data, with a few percentage value discrepancies.
9
Review of Human Reliability Assessment Methods
A. G. Reis, R. A. Neves, R. Ceni et al. · Offshore Technology Conference · 2024 · 149 citations
The application of ATHEANA: a technique for human error analysis
C.M. Thompson, S.E. Cooper, A.M. Kolaczkowski et al. · 2002 · 35 citations · Full text
Engineering, Psychology, Ergonomics +12