Illinois Digital Environment for Access to Learning and Scholarship (University of Illinois at Urbana-Champaign) · 1993 · 22 citations · 15 references
Open access
EngineeringMechanical EngineeringAir ConditioningHeat TransferHvac SystemsEvaporative CoolingHeat ConductionHeat Transfer FundamentalsRefrigerationRefrigeration SystemsAir Conditioning PerformanceEvaporation EfficiencyEvaporator PerformanceEvaporatorsHeat Flux MeasurementHeat Transfer CoefficientsHeatersMass Flux
Experimental heat transfer coefficients for R-134a, MP-39, and R-12 are reported \nherein. Tests were conducted using a single-tube evaporator test facility. The test section \nused was a 2.43 m (8-foot) long, 7.04 mm (0.277-in) inside diameter, horizontal, smooth \ncopper tube. Heat was applied to the test section using electric resistance heaters. Test \nparameters were varied as follows: mass flux, 25-100 kg/m2-s (19-76 klbm/ft2-hr); heat \nflux, 2-10 kW/m2 (600-3200 Btu/hr-ft2); quality, 10-90 percent; saturation temperature, \n-15 to 5??C (5 to 41??F). The heat transfer coefficients for R-134a were higher than those \nof R-12 using equivalent mass flux and cooling capacity bases. The heat transfer \ncoefficients for MP-39 were lower than those of R-12 using equivalent mass flux and \ncooling capacity bases. The correlations of Shah and Kandlikar were compared with the \nexperimental heat transfer coefficients. An empirical correlation was developed for the \nwavy-stratified flow pattern occurring with the low mass fluxes. For correlating \npurposes, some high mass flux data with annular flow patterns, reported previously, are \nalso included.