Design, Building, and Baseline Testing of an Apparatus Used to Measure Evaporation Characteristics of Ozone-Safe Refrigerants

J.P. Wattelet

Illinois Digital Environment for Access to Learning and Scholarship (University of Illinois at Urbana-Champaign) · 1990 · 11 citations · 9 references

Full text

Open access

Concepts

Abstract

Chlorofluorocarbons are the primary refrigerants used in vapor-compression air
\nconditioning and refrigeration systems. Environmental concerns, such as the ozone depletion
\neffect of chlorofluorocarbons, have led to an international agreement on the reduction and eventual
\nelimination of these refrigerants. Alternative, ozone-safe refrigerants have been developed and
\ntheir evaporation characteristics need to be assessed. A single-tube evaporation test facility has
\nbeen designed and built to measure these characteristics. An instrumented, eight-foot long
\n(2.44 m), 0.402-inch (10.21 mm) inside diameter evaporation test section equipped with SCRcontrolled,
\nsurface wrapped heaters is the main feature of the design. Leak testing and a
\npreliminary system shakedown have been successfully completed. Baseline testing using CFC-12
\nas the reference fluid has been conducted. Mass fluxes were tested over the range of 100,000
\nIbmlhreft2 (135 kg/sem2) to 400,000 Ibmlhreft2 (540 kg/s??m2), and heat fluxes were varied from
\n1600 Btulhreft2 (5.1 kW/m2) to 6400 Btulhr??ft2 (20.4 kW/m2). Evaporation temperatures were
\nbetween 40 OF (4.4 OC) and 52 OF (11.1 OC) with inlet qualities of 20 to 60 percent. Expected
\ntrends in the data were observed. Average heat transfer coefficients compared closely with average
\nheat transfer coefficients calculated from correlations of Chaddock-Noerager, Kandlikar, Shah,
\nand Pierre. However, uncertainty in both temperature and heat input measurements require further
\nimprovements to the system. Additional capacity of the chiller system is also needed so that lower
\nevaporation temperatures and larger heat additions to the test refrigerant can be maintained.