Simultaneous measurements of infiltration and intake in an office building

Andrew K. Persily, L. K. Norford

ASHRAE winter conference papers · 1987 · 16 citations · 0 references

Concepts

Abstract

Tracer gas decay measuring techniques exist to determine whole building air exchange rates. This paper presents two new measuring techniques to determine simultaneously both the amount of air exchange due to intentional outdoor air intake and the amount due to uncontrolled envelope infiltration. One of these techniques was applied to a new office building as a demonstration of the procedure, and to investigate the air exchange characteristics and mechanical ventilation system performance in this particular building. Using a tracer gas measuring technique in combination with multithermistor airflow-rate measuring systems, intake and infiltration rates were measured under a range of weather conditions and outdoor air intake rates. The results indicate that the outdoor air intake rates for this building are often well below their design values, a significant percentage of the net air exchange rate of the building is due to envelope leakage, and the amount of envelope leakage is dependent primarily on the outdoor air intake rate.