IEEE Transactions on Power Delivery · 2023 · 20 citations · 8 references
EngineeringElectrical EngineeringCircuit TheoryPower ElectronicsRenewable Energy SystemsPower Grid AnalysisPower QualityPower System ReliabilityPower SystemsProtection SystemsTransmission LinesComparatorsDistance ProtectionFault Protection SystemsProtection RelayingRelay ProtectionRelays
Unconventional fault currents of inverter-based resources (IBRs) can adversely impact distance relays. Despite extensive investigation in the literature, the available studies on this topic mostly suffer from three main shortcomings: (i) they consider only the apparent-impedance-based implementation method of distance protection and do not cover the methods used by relay manufacturers to realize the distance element, (ii) they focus on only the relays that protect the direct tie-lines of IBRs, severely limiting the benefits of these studies for future IBR-centric grids, and (iii) they do not consider the requirements of recent grid codes and standards for the low-voltage ride-through current of IBRs. This article addresses these three shortcomings. Part I of this article is on distance relays that use phase comparators.
8
Ali Hooshyar, Maher A. Azzouz, Ehab F. El‐Saadany · IEEE Transactions on Power Delivery · 2014 · 226 citations
Engineering, Electrical Engineering, Critical Infrastructure Protection +16
Ali Hooshyar, Maher A. Azzouz, Ehab F. El‐Saadany · IEEE Transactions on Power Delivery · 2014 · 129 citations
Engineering, Electrical Engineering, Fault-tolerant Systems +16