2006 · 11 citations · 6 references
EngineeringElectrical EngineeringMaterials ScienceBuilding DiagnosticsCondition AssessmentMaterials CharacterizationElectrical CharacterizationElectrical MeasurementElectrical System DiagnosticsInsulation MaterialsInsulation SystemsMaterial Degradation AssessmentCable InsulationCondition Monitoring Of InsulationDielectric MeasurementInsulation Degradation AssessmentInsulation Degradation DiagnosisInsulation DiagnosticsInsulation MonitoringTime-domain Reflectometry
The paper presents a methodology for successful localization of degraded insulation in medium voltage cables. Extensive work has been performed on development of cable models and characterization of new and degraded cable material to support the diagnostic technique. A non-destructive technique has been developed using differential time domain reflectometry (TDR) measurements. The main application has been localization of water treed sections of XLPE cables where the voltage dependence of the permittivity of water treed insulation has been used as diagnostic criteria.
6