Development of a hot-line diagnostic method for XLPE cables and the measurement results

Akira Nakajima, N. Kashiwagi, T. Murata, Shunsuke Takahashi, Osamu Fukuda, S. Kitai, K. Tokumaru, K. Hirotsu

IEEE Transactions on Power Delivery · 1989 · 17 citations · 0 references

Concepts

Abstract

Hot-line diagnosis is needed to avoid breakdowns of XLPE (cross-linked polyethylene) cables due to water trees. The authors superposed a low DC voltage on an AC commercial voltage, measured the DC component of the current which passed through the insulation, and discovered that the DC component had a close relationship with the degradation caused by water trees. A hot-line diagnostic measurement system based on this DC superposition method was developed. The old cables that were removed and cables now in use were measured with the system; the results are reported.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>