IEEE Transactions on Industry Applications · 1994 · 99 citations · 6 references
Electrical EngineeringEngineeringDetailed AnalysisCharacteristic Converter Harmonics5Th HarmonicPower Electronics ConverterElectric Power ConversionPower InverterPower ElectronicsElectric Power QualityHarmonic MitigationElectromagnetic CompatibilityHigher Order Harmonics
Classical methods for the determination of six-pulse power converter harmonic currents often do not adequately describe the harmonic current magnitudes actually found in practice. To accurately determine the magnitude of characteristic converter harmonics, a calculation procedure which takes into account the ripple of the DC current reflected back into the AC line current must be performed. Various methods from the literature for the determination of six-pulse power converter harmonic currents are compared and a method which takes the fast Fourier transform of the time domain equations is described. Evaluation of these ripple effects tends to increase the magnitude of the 5th harmonic while decreasing the magnitudes of higher order harmonics. Noncharacteristic harmonic orders or frequencies will sometimes also be encountered. These orders typically will be less than the 5th and can be of concern because of possible coincidence with 5th harmonic filter anti-resonance points.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>
6
Harmonic Reduction In Group-Connected Generators-HVDC Convertor
J. Arrillaga, Yonghe Liu, C.S. Crimp et al. · 2005 · 365 citations
Rectifier Circuits—Theory and Design
Rafael Waters · Electronics and Power · 1965 · 159 citations
L.G. Dobinson · Electronics and Power · 1975 · 28 citations