Availability of corona cage for predicting audible noise generated from HVDC transmission line

Yukio Nakano, Yoshitaka Sunaga

IEEE Transactions on Power Delivery · 1989 · 42 citations · 4 references

Concepts

Abstract

The authors examine the feasibility of using a corona cage to predict audible noise (AN) generated from an HVDC (high-voltage direct current) transmission line. The possible use of the cage is based on the assumption that generation quantities of AN and corona current are determined by F/sub max/ (the 'true' maximum conductor surface gradient in the presence of space charge) regardless of the surrounding electrode arrangement. This assumption has been verified by tests using corona cages and a test line. The results indicate that a corona cage is indeed suitable for predicting AN generated from HVDC transmission lines. It is applicable to DC lines with any line configuration and any polarity arrangement.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

References

4