IEEE Transactions on Energy Conversion · 2001 · 146 citations · 9 references
EngineeringElectrical EngineeringCircuit TheoryElectric MachinesPower ElectronicsBrushless Dc MachinesElectric MotorsInduction MachinesThree-phase CircuitsThree-phase MachinesVoltage RegulationInduction Motor TheoryInduction MotorsSteady-state VoltageThree-phase Induction MachinesThree-phase Induction MotorsThree-phase MotorsUnbalanced Three-phase SystemsVoltage Unbalance
Analysis of the steady-state performance of an induction motor connected to unbalanced three-phase voltages is presented. The index of voltage unbalance used in this paper is the complex voltage unbalance factor (CVUF) that consists of the magnitude and the angle. In addition to formulation and discussion of the motor operating characteristics under voltage unbalance, special emphasis is placed on the effect of the angle of the CVUF on the motor. It is found that the angle of the CVUF is also an important factor that merits particular attention in analyzing voltage unbalance issues.
9