IEEE Transactions on Power Delivery · 1989 · 21 citations · 5 references
Natural SciencesMaterials EngineeringMaterials SciencePolymer ChemistryPolymer EngineeringPolymer MaterialsInsulation MaterialsInsulation SystemsMaterial PerformanceAccelerated Aging TestsAccelerated WeatheringAccelerated Weathering TestsCable InsulationElectrical Insulation MaterialsPolymer Insulation MaterialsPolymeric InsulationWeathering Of Polymer Materials
The authors present the results of fog chamber tests performed to compare the contamination performance of 25 kV class outdoor polymeric cable terminators. The experiments were conducted in high-conductivity (>or=1200 mu s/cm) fog. The effects of weathershed material and design, method of stress relief, and experimental conditions on the contamination performance are discussed. It is shown that the weathershed material and design have a greater influence on the contamination performance than the method of stress relief. The results indicate that the method of stress relief does not improve contamination performance under normal operating stress. For terminators using good track-resistant materials, satisfactory performance can be obtained even with a 50% reduction in the leakage distance provided.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>
5