IEEE Transactions on Power Delivery · 1992 · 22 citations · 2 references
EngineeringElectrical EngineeringCircuit TheoryCritical Infrastructure ProtectionEnergy SystemsHigh-performance InsulationInsulation SystemsPower Grid AnalysisPower SystemsTransmission LinesElectric Power TransmissionElectrical Power InfrastructureElectricity DistributionInsulation PerformanceLoad Flow AnalysisPower TransmissionsSystem Response AnalysisSystem Stability
Conversion of an existing double-circuit 115 kV overhead transmission line near Binghamton, New York to six-phase operation will provide a commercial demonstration of feasibility of high phase order power transmission. Analyses of insulation performance, corona and field effects, and a load flow and system stability have been performed as part of the preliminary engineering for this project. It is shown that conversion of the Goudey-Oakdale double-circuit 115 kV line to 93 kV six-phase is possible if insulator strings are lengthened to 8 units/string. This results in a 40% increase in thermal loading capacity and a doubling of surge impedance loading, while meeting all applicable electrical environmental requirements.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>