International Journal of Refrigeration · 2022 · 25 citations · 26 references
EngineeringMechanical EngineeringEnergy SystemsHeat TransferThermodynamicsHeat ExchangersHvac System DesignRefrigerationRefrigeration CyclesRefrigeration SystemsThermal ManagementEnergy ConsumptionEnergy PerformanceHeat Exchanger PerformanceHeat RejectionRefrigerantsRefrigeration TechnologyVapor Compression CycleVapor Compression Refrigeration Cycle
This work analyses the influence of the Internal Heat Exchan ger (IHX) on the energy performance of a vapor compression cycle associated with a freezing cabinet using different R404A low-GWP alternatives. Among them, the refrigerants R454C (GPW100=146), R455A (GPW100=146), R468A (GPW100=146), R290 (GPW100=5) and R1270 (GPW100=1.8) have been tested in a horizontal freezing cabinet maintaining a product target temperature of -20°C at the heat rejection temperatures of 20, 30 and 40°C. The results from tests show that the use of the IHX reduces energy consumption in all scenarios without significantly increasing the compressor's discharge temperature. For a test period of 16 h, the refrigerants that offer better reductions are R404A and R1270, followed by R455A, R290, R454C and R468A. The maximum energy saving is rated to 9.2% at the heat rejection temperature of 40°C, demonstrating that the enhancement of the IHX is better as higher the heat rejection conditions are.
26