Energies · 2021 · 12 citations · 57 references
EngineeringEnvironmental EngineeringEnvironmental SciencesAir PollutionIndoor Environmental QualityVentilationAir PollutantsAir Pollution ModelingAir QualityIndoor Air PollutionVentilation ModelingVentilation SystemsAir ExchangeCfd SimulationIndoor Air QualityIndoor Air Quality ImprovementJet VentilationVentilation EffectivenessVentilation PerformanceVentilation System Simulation
The indoor air quality (IAQ) of severely polluted toilets is associated with the transmission of diseases. Computational fluid dynamics (CFD) methods and experimental measurements were used to analyze the diffusion characteristics of pollutants. This study investigated the diffusion characteristics and normalized concentration of ammonia and hydrogen sulfide pollutants under three ventilation systems—mixing ventilation (MV), personalized ventilation (PV), and impinging jet ventilation (IJV)—in a public toilet. The mean age of air (MAA) and air exchange efficiency (AEE) were also analyzed in our study. The results show that the MV scheme has a poor removal effect on pollutants compared with PV and IJV. IJV has advantages in reducing the normalized concentration of pollutants and improving the IAQ. Increasing the number of air changes per hour (ACH) may lead to a longer MAA and reduced air exchange efficiency. Choosing an appropriate number of air changes is very important to improve the IAQ in the toilet.
57
Stephen S Lim, Theo Vos, Abraham D Flaxman et al. · The Lancet · 2012 · 12K citations · Full text
Public Health, Chronic Disease Control, Chronic Disease Prevention +17