ASHRAE winter conference papers · 1986 · 37 citations · 0 references
ArchitectureArchitectural EngineeringBuilding ScienceAir ConditioningHvac SystemsVentilationAir Conditioning EquipmentAir Conditioning SystemsAir Temperature EffectsHvac System DesignHvac System SimulationVariable Air Volume SystemsAir Conditioning ModelingAirflow ControlEnergy Use ReductionFan Energy EfficiencyFan Power ConsumptionHvac Energy OptimizationSupply Temperature ControlVariable Air Volume System Simulation
A VAV system in a commercial office building in central New Jersey has been modeled, with DOE-2 and a variable-base bin method, to assess control strategies that lead to reduce HVAC costs with no decrease in comfort. The goal is to minimize the sum of fan and heating/cooling power while providing sufficient air to maintain desired office temperatures and air quality. With the 55 F (12.8/sup 0/C) supply air temperature specified by the HVAC designer, fan energy is kept low at the expense of the chillers. Raising the supply air temperature to 60 F (15.6/sup 0/C) makes more use of outdoor air in temperate weather and reduces the chiller energy consumption by a predicted 33 MWh/year while increasing fan power by only 4 MWh, for a net savings in combined fan and chiller power of 23%. An additional 9 MWh of net fan and chiller energy savings can be achieved by varying the supply air temperature with outdoor temperature.