IEEE Transactions on Power Systems · 2021 · 44 citations · 12 references
EngineeringElectrical EngineeringSystems EngineeringCircuit TheoryPower ElectronicsSystems ModelingPower Distribution ControlPower Grid AnalysisPower SystemsPower Transmission SystemsState EstimationTransmission LinesAdmittance AnalysisAdmittance MatrixDistribution Network ModelingImpedance MatrixNetwork Admittance MatrixPower Flow AnalysisPower System ModellingTransmission Line Power Flow
Topology identification and parameter estimation form the basis for the operation and control of the distribution network with little or no observability. This paper proposes a method to estimate the admittance matrix for open-loop distribution networks based only on active/reactive power injection and voltage magnitude data. We derive the linear relationship between the admittance matrix and the measurements based on decoupled linear power flow (DLPF) equations. A total least squares regression method is proposed based on analysis of the characteristics of the open-loop grid admittance matrix. Case studies on the IEEE 33-bus system demonstrate the proposed method's effectiveness, accuracy, and efficiency.
12