Abstract

Cfu were significantly lower in LAF at both 100% and 50% air influx. It is possible to reduce fresh air influx in LAF operating theatres by 50%, significantly reducing energy consumption, while still maintaining cfu and particle counts below the ISO classification threshold required for THA surgery.