IEEE Power Engineering Review · 2002 · 27 citations · 0 references
EngineeringElectrical EngineeringPower ElectronicsRenewable Energy IntegrationRenewable Energy SystemsDc-ac InvertersPower Electronics For Renewable EnergyPower Grid AnalysisRenewable Energy Power ConversionSolar Energy SystemsSolar Photovoltaic SystemsFrequency DriftGrid-connected InvertersGrid-connected Photovoltaic SystemsInvertersIslanding DetectionPhase-shift ControlPhotovoltaic InvertersTerminal Voltage Variation
The traditional frequency-shift methods for islanding detection of grid connected PV inverters (the active frequency-drift method and the slip mode frequency-shift method) become ineffective under certain paralleled RLC loads. The automatic phase-shift method is proposed in this paper to alleviate this problem. The method is based on the phase shift of the sinusoidal inverter output current. When the utility malfunctions, the phase-shift algorithm keeps the frequency of the inverter terminal voltage deviating until the protection circuit is triggered. Simulation and experiments are performed for verification.