EngineeringElectrical EngineeringCritical Infrastructure ProtectionFault-tolerant ComputingFault-tolerant SystemsDiagnosticsElectrical System DiagnosticsElectrical System TestingFault DetectionFault DiagnosisProtection SystemsCable Fault IdentificationCurrent-based Fault DiagnosisIncipient Fault DetectionOperational SecurityPermanent FaultsTransient Overvoltages
This paper presents an operational experience with incipient faults: it has been observed that 10 to 15% of cable faults are preceded by incipient faults. Practically all incipient faults become permanent faults in the period between a few seconds to few weeks. Incipient faults occurring in fast successions create considerable overvoltages and induce faults on other feeders. A method has been presented to detect incipient faults in a secure and reliable way. The method is secure by checking consistency of the load before and after the event, checking if the event is a single phase event, and checking for duration and consistency between the superimposed fault component and the ground current. The presented method has been implemented and tested using recorded field cases and on a digital simulator.
1
Electrical Insulation in Power Systems
J.J. Shea · IEEE Electrical Insulation Magazine · 1998 · 74 citations