IEEE Power Engineering Review · 1985 · 14 citations · 0 references
Natural SciencesElectrical EngineeringCritical Infrastructure ProtectionElectromagneticsGround ImprovementElectrical InstallationLightning CurrentLightning PhysicsLightning ProtectionLightning SafetyThunderstorm ElectrificationLightning Protection DesignLightning Protection For Power SystemsLightning Protection Of Critical InfrastructureLightning Protection Of Power LinesLightning Protection Of SubstationsLightning Protection SystemsLightning Surge ProtectionStruts Systems
Special zinc oxide series gapped line arresters were installed on Appalachian Power Company 138 kV lines having high tower footing resistance and severe lightning exposure. This effort was part of an experiment to explore means of reducing lightning flashovers in exposed locations where low ground resistances are not feasible. Because of possible future voltage uprating of these lines, the arresters were built in the form of high strength nonporcelain mechanical struts, designed to limit phase conductor swing. This paper describes the field installation of these experimental arresters and their instrumentation and reports operating experience in 1983.