Overvoltage characteristics in symmetrical monopolar HB MMC-HVDC configuration comprising long cable systems

Max Goertz, Simon Wenig, S. Beckler, Carolin Hirsching, Michael Suriyah, Thomas Leibfried

Electric Power Systems Research · 2020 · 11 citations · 6 references

DOIFull text

Open access

Concepts

Abstract

• Standardized test levels for high voltage direct current cable systems are not yet available. • Electromagnetic transient studies are an essential tool for insulation co-ordination. • Overvoltage analysis for the symmetrical monopolar scheme configuration. • Overvoltage parameters such as peak value, rise time and gradient are dependent on the cable route length. This contribution focuses on high voltage direct current (HVDC) transmission systems comprising modular multilevel converters (MMC) equipped with half-bridge (HB) submodules and analyses cable voltage stresses during various station internal as well as dc side faults. In order to examine relevant overvoltage characteristics affecting HVDC cable systems, a systematic approach to evaluate overvoltage stresses is presented and an extensive set of time-domain simulations is analysed for schemes operating in symmetrical monopolar configuration. Obtained results are relevant for considerations on insulation co-ordination of HVDC cable systems and for a comprehensive definition of high voltage testing requirements.

References

6