Application of low global warming potential refrigerants for room air conditioner.

A Fujitaka, T. Shimizu, Shozo Sato

2010 · 27 citations · 7 references

Concepts

Abstract

An application of the low Global Warming Potential (GWP) refrigerants, HFO-1234yf (2,3,3,3-tetrafluoropropene) and R32/HFO-1234yf mixtures, for the room air conditioner was performed. Acid number of polyolester refrigeration oil for R410A has greatly increased after aging with HFO-1234yf containing air. HFO-1234yf breakdown products such as hydrogen fluoride may cause this phenomenon. However, other materials compatibility has been almost identical to R410A. Using R410A room air conditioner, the drop-in tests of HFO-1234yf and R32/HFO-1234yf mixtures were carried out. The performance of HFO-1234yf is significantly lower than that of R410A as a result of the pressure drop increasing. The performance of R32/HFO-1234yf improves as the R32 concentration becomes richer. The COPs of R32/HFO-1234yf (50/50 wt%) under cooling and heating conditions are 95 and 94% of those of R410A respectively.

References

7