2020 IEEE International Conference on Power Electronics, Smart Grid and Renewable Energy (PESGRE2020) · 2020 · 19 citations · 9 references
EngineeringElectrical EngineeringInstrumentationMetrologyPerformance MeasurementDigital InstrumentationDigital Signal ProcessingTime-frequency AnalysisUnits Of MeasurementHamming DistancePhasor Measurement UnitsPrecision Measurement
According to the standard C37.118.1, Phasor Measurement Units (PMU) can be broadly classified into two classes: Measurement (M) and Performance (P), where P-Class is used when faster output latency is required and M-Class is used for measurement applications which requires high precision. The standard presents Hamming window as a reference algorithm for M-Class PMU whereas, in this paper we use Blackman window algorithm. The performance of M-Class PMU is analyzed with both the algorithms by taking two case studies in which input given to the PMU is contaminated with different levels of harmonics, inter-harmonics and frequency ramps in each case and it is found that, the errors in frequency and rate of change of frequency (ROCOF) measured by PMU are reduced by a factor of >100 with the Blackman window algorithm when compared to a Hamming window algorithm (which is specified in the standard).
9
IEEE Standard for Synchrophasors for Power Systems
K.E. Martin, G. Benmouyal, Mark Adamiak et al. · IEEE Transactions on Power Delivery · 1998 · 382 citations
Engineering, Electrical Engineering, Systems Engineering +16