The Influence of Power Frequency Deviation on the Active and Reactive Power Measurement Error with the Application of DFT

Andrey N. Serov, Alexander Novitskiy, Alexander A. Shatokhin, Steffen Schlegel, Ekaterina A. Dolgacheva, Dirk Westermann

2019 · 27 citations · 10 references

Concepts

Abstract

In this article a study of the method of measuring the parameters of electric power was made, based on the use of discrete Fourier transformation (DFT). The voltage and current of the real electrical networks differ from the sine wave: they may include harmonics, supraharmonics and noise. The frequency of real electrical networks may deviate from the nominal value, and it may cause the additional measurement errors for the spectral measurement and power characteristics. To ensure the required measurement error, an additional frequency measurement is performed, followed by a sample rate adjustment, in such way, that the integer number of input signal periods equals the number of samples, which equals to power of two or four. The influence of the input signal parameters, sampling rate, measurement time and frequency measurement error on the measurement error of the active power parameters is considered. Analytical expressions, allowing to estimate the measurement error for parameters of active power, which are caused by inaccurate adjustment of sampling frequency under frequency of an electric network, are received. The reliability of the obtained analytical expressions is verified by comparing them with the results of mathematical modeling in Simulink 8.