Case Studies in Thermal Engineering · 2019 · 29 citations · 8 references
EngineeringIndustrial EngineeringManufacturing EngineeringAir ConditioningEnergy ManagementHeat TransferEnergy ConversionEnergy-efficient ManufacturingIndustrial Energy SystemsRefrigerationRefrigeration SystemsWater-saving TechnologiesChiller SystemsCompressed Air SystemsCooling Water SystemsEnergy ConsumptionEnergy Savings AssessmentEnergy Simulation ModelingEnergy-efficient Production SystemsOperational Energy Consumption
This study integrates a fab energy simulation (FES) tool and energy conversion factors to analyze energy consumption and identify energy savings opportunities of high-tech manufacturing factories. The data used is the 169,124 MW h annual energy consumption of a Taiwanese semiconductor manufacturing fab. We proposed a compressed/clean dry air (CDA) system as a two-pressure system using a heated-type dryer. The proposed method achieved 3050 MW h as the highest energy savings in the CDA system compared to the original fab data. The results also indicate that lowering the make-up air unit (MAU) operating temperature caused significant energy savings for the high-temperature water chiller system. When the outlet air temperature of the MAU system was 14 °C, the maximum energy savings were 3532 MW h. In addition, the process cooling water (PCW) system could potentially save energy by reducing the pumping head of water in its open system. Therefore, we suggested a closed PCW system that reached a maximum energy saving of 1541 MW h.
8
Power consumption of semiconductor fabs in Taiwan
Shih-Cheng Hu, Yew Khoy Chuah · Energy · 2003 · 129 citations
Engineering, Electrical Engineering, Semiconductor Devices +3
Various Energy-Saving Approaches to a TFT-LCD Panel Fab
Cheng-Kuang Chang, Tee Lin, Shih-Cheng Hu et al. · Sustainability · 2016 · 29 citations · Full text
Engineering, Electrical Engineering, Mechanical Engineering +16