International Journal of Numerical Methods for Heat & Fluid Flow · 2019 · 57 citations · 31 references
EngineeringMechanical EngineeringEnergy SystemsHeat TransferHvac SystemsAir Conditioning SystemsAir Handling UnitsEnergy ConversionExergy AnalysisHeat ExchangeHeat ExchangersAir Handling Unit ModelingAir-to-air Heat ExchangersBalance EquationsEnergy ConsumptionExergy BalanceHeat Exchanger EfficiencyHeat Transfer MechanismsSecond Law Efficiency
Purpose This study aims to simulate the flow and heat transfer through an air handling unit to reduce its energy consumption by a novel creative idea of using an air-to-air heat exchanger. Design/methodology/approach To do this, both first and second laws of thermodynamics energy and exergy balance equations were solved numerically by an appropriate developed computer code. Findings Using the air-to-air heat exchanger in dry conditions decreases the cooling coil load by 0.9 per cent, whereas the reduction for humid conditions is 27 per cent. Similarly, using air-to-air heat exchanger leads to an increase in the first law of efficiency in dry and humid conditions by 0.9 per cent and 36.8 per cent, respectively. Originality/value The second law of efficiency increases by 1.55 per cent and 2.77 per cent in dry and humid conditions, respectively. In other words, the effect of using an air-to-air heat exchanger in humid conditions is more than that in dry conditions.
31
Optimal exergy control of building HVAC system
Meysam Razmara, Mehdi Maasoumy, Mahdi Shahbakhti et al. · Applied Energy · 2015 · 126 citations
Engineering, Architectural Engineering, Building Science +12