IEEE Transactions on Industry Applications · 2019 · 56 citations · 35 references
AgricultureElectrical EngineeringPower ElectronicsRenewable Energy IntegrationRenewable Energy SystemsDistributed Energy ResourcesMicrogridsSmart Grid SystemsSolar Photovoltaic SystemsVoltage RegulationWind Energy SystemsActive ControlActive Power ControlGrid SynchronizationMaximum Power Point TrackingPhotovoltaic-diesel Hybrid SystemsPower Quality ImprovementVariable-speed Wind TurbinesWind-diesel Hybrid Systems
In this paper, a comprehensive controller of a standalone microgrid is implemented, which has three dispersed generation units based on a wind, solar photovoltaic (PV) array, and a diesel generator (DG). The power ratio variable step perturb and observe method is applied to achieve maximum power point tracking of a solar PV array and a variable speed wind turbine coupled a permanent magnet brushless dc generator without rotor/wind speed sensors. Moreover, to ensure perfect synchronization of a DG to the point of common coupling (PCC), a control algorithm is developed, which is based on in-phase and quadrature units. An active power control based on proportional–integral controller with anti-windup, is used for voltage and frequency regulation. The <italic xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">LCL</i> filter based on virtual resistor, is used for power quality improvement at PCC. Simulation and test results are presented for the validation of the proposed system using a prototype of 2 kW in the laboratory.
35
Jörg Dannehl, Friedrich W. Fuchs, Steffan Hansen et al. · IEEE Transactions on Industry Applications · 2010 · 551 citations