IEEE Transactions on Instrumentation and Measurement · 2019 · 25 citations · 8 references
EngineeringElectrical EngineeringMaintenance EngineeringMechanical Behavior Of MaterialsPower ElectronicsElectrical System DiagnosticsInsulation MaterialsInsulation SystemsMaterial Degradation AssessmentNetwork ReliabilityStructural ReliabilityAgeing EffectsAging CharacterizationCable InsulationCable Insulation IntegrityInsulation AgingPartial DischargePartial Discharge TestingTan Delta
Medium-voltage cable joints are one of the critical components of the distribution networks. They represent the first cause of faults and outages. Among the others, partial discharge, dielectric, and temperature measurements are the typical tests performed for investigating over the early aging of such critical components. In this paper, a new study has been completed correlating the cable joint tangent delta (Tanδ ) value to the external pressure applied on the insulating material surrounding the joint. Results confirm the presumed correlation. In fact, an increase of pressure results in a Tanδ decrease, hence in an extension of the cable joint working life.
8
Impacts of temperature on the distribution of electric-field in HVDC cable joint
Yanjun Qin, Nanqiang Shang, Minghe Chi et al. · 2015 · 22 citations