Energies · 2019 · 44 citations · 72 references
EngineeringElectrical EngineeringEnergy SystemsPower ElectronicsRenewable Energy SystemsDc-dc ConvertersPower SystemsRenewable Energy Power ConversionSolar CellsSolar Energy SystemsSolar Photovoltaic SystemsDc-dc Converter TopologiesElectrical System AssessmentElectrical System IntegrationPhotovoltaic SystemsPower Conversion For Photovoltaic SystemsSolar Photovoltaic InstallationSolar Photovoltaic IntegrationSolar Photovoltaic Power Systems
Since building-integrated photovoltaic (BIPV) modules are typically installed during, not after, the construction phase, BIPVs have a profound impact compared to conventional building-applied photovoltaics on the electrical installation and construction planning of a building. As the cost of BIPV modules decreases over time, the impact of electrical system architecture and converters will become more prevalent in the overall cost of the system. This manuscript provides an overview of potential BIPV electrical architectures. System-level criteria for BIPV installations are established, thus providing a reference framework to compare electrical architectures. To achieve modularity and to minimize engineering costs, module-level DC/DC converters preinstalled in the BIPV module turned out to be the best solution. The second part of this paper establishes converter-level requirements, derived and related to the BIPV system. These include measures to increase the converter fault tolerance for extended availability and to ensure essential safety features.
72
Thin‐film silicon solar cell technology
A. Shah, H. Schade, M. Vaněček et al. · Progress in Photovoltaics Research and Applications · 2004 · 708 citations · Full text