Energies · 2019 · 14 citations · 33 references
EngineeringElectrical EngineeringDistributed SystemsPower ElectronicsRenewable Energy SystemsDc-ac InvertersMicrogridsPower ControlDroop ControlDynamic ResponseInverter ControlInverter SystemsInvertersReactive Power CompensationReactive Power ControlVoltage
In this paper, the effect of the line impedance difference between various inverters on power sharing with the traditional droop control method is fully analyzed. It reveals that the line impedance difference causes a significant reactive power error. An improved droop control method to eliminate the reactive power errors caused by the line impedance errors is proposed. In the proposed method, a voltage compensation determined by the actual reactive power error between the local inverter and the average one is added into the local voltage reference based on the CAN communication. Even when the communication is interrupted, the controller will operate with the last value of the average power, which still outperforms the traditional method. The effectiveness of the proposed control method is verified by simulation and experimental results, which show the proposed method possesses the better power sharing performance and dynamic response.
33
Control of Power Converters in AC Microgrids
Joan Rocabert, Álvaro Luna, Frede Blaabjerg et al. · IEEE Transactions on Power Electronics · 2012 · 3.6K citations
Engineering, Electrical Engineering, Distributed Systems +16
Josep M. Guerrero, J. Matas, Luis García de Vicuña et al. · IEEE Transactions on Industrial Electronics · 2007 · 1.1K citations
Engineering, Electrical Engineering, Distributed Systems +16
Wei Yao, Min Chen, J. Matas et al. · IEEE Transactions on Industrial Electronics · 2010 · 843 citations · Full text